| PERFORMANCE |
| Measurement Range (RH) |
0-100% RH |
| Measurement Range (T)-Configurable on Request |
0 to +50°C 0 to +100°C -20 to +80°C -30 to +20°C -30 to +70°C |
| Accuracy RH @ 23°C |
<±2% RH (5-95% RH) |
| Accuracy T @ 23°C |
Pt100 Ω 1/3 DIN direct ±0.2°C Current output ±0.3°C |
| Stability - RH Sensor |
<±1% RH/year |
| Response Time |
<10 sec typical (for 90% of the step change) |
| ELECTRICAL INPUT/OUTPUT |
| Output Signal (RH)-Configurable on Request |
4–20 mA 0–1 V, 0–5 V, 0–10 V |
| Output Signal (T)-Configurable on Request |
4–20mA 3-wire 100 Ω 1/3 DIN direct Pt100 0–1 V, 0–5 V, 0–10 V |
| Supply Voltage |
Output 4–20mA: E = 12–30 VDC Output 0–10V: E = 15–30 VDC Output 0–5V: E = 10–30 VDC Output 0–1V: E = 8–30 VDC |
| Load Resistance |
Output 4–20mA: Rload < (Uv-9)/0.02 Output 0–10V: R > 10 k Ω Output 0–5V: R > 5 k Ω Output 0–1V: R > 1 k Ω |
| Current Consumption |
Analogue loops 2 x 20mA max |
| OPERATING CONDITIONS |
| Operating Temperature |
Measurement head: -30 to +85°C Housing: -30 to +70°C Storage: -40 to +70°C |
| Operating Humidity |
Sensing element: 0–100% RH (non-condensing) Housing: 0–98% RH (non-condensing) Storage: 0–98% RH (non-condensing) |
| MECHANICAL SPECIFICATIONS |
| Ingress Protection Sensor |
IP65 |
| Housing Material |
PPO |
| Electrical Connections |
Screw terminals, tightening torque 1.5mm2 max Output via wire to wire pitch from 3.5 to 6 mm diameter |
| Dimensions |
Housing: 80 x 80 x 34 mm Probe: L=85mm, ø12mm |
| Weight |
100g |