The new 40/40UV Flame Detector detects hydrocarbon-based fuel and gas fires, invisible hydrogen flames, and fires from hydrides, ammonia, silane and other organics. The 40/40U-UB is the most durable and weather resistant UV flame detector currently on the market. Its new features include a heated window to eliminate condensation and icing; HART capabilities, for digital communications; lower power requirements; and a compact, lighter design.
Due to increased reliability, the 40/40 Series warranty period has been extended to 5 years and is approved to IEC 61508 Safety Integrity requirements of SIL2 (TUV).
The model 40/40UB includes a Built-in-Test (BIT) feature, whereas the 40/40U model does not.
Note: This type of detector should not be exposed to UV radiation sources such as welding, sparks, and electric arcs as it will cause false alarms.
Features
- UV Spectrum Design
- 3-Second Response
- Automatic and Manual Built-In-Test (BIT) - to assure continued reliable operation
- Heated Window - for operation in harsh weather conditions (snow, ice, condensation)
- Multiple Output Options for maximum flexibility and compatibility
- Relays (3) for Alarm, Fault and Auxiliary
|
|
- HART Protocol for maintenance and asset management
- RS-485, Modbus Compatible
- High Reliability - MTBF - minimum 150,000 hours
- 5-Year Warranty
- User Programmable via HART or RS-485
|
Approvals
Hazardous Area Ex Approvals: FM , CSA , ATEX , IECEx , GOST R , CEPEL , CIMFR |
Functional Approvals: FM , LPCB (EN54-10) |
Reliability Approvals: TUV (SIL2) |
CPD Certificate of Conformity: LPCB (U) , LPCB (UB) |
Other Approvals: GOST K , CAL FIRE | |