西门子SIEMENS燃烧器程控器LFL1.322
价格:电议
地区:安徽省 芜湖市
电 话:0553-5865552
手 机:15385535339
传 真:0553-5865552
加工定制:否品牌:Siemens/西门子型号:LFL1.332

LFL1...系列燃气燃烧器控制器

品牌:SIEMENS(西门子)

产地:德国

 产品介绍

The burner controls of the LFL1... range are designed for the control and supervision of forced draught gas burners of both expanding flame and interrupted pilot construction of medium to high capacity. They are universally applicable and can be used for both multistage and modulating burners as well as for dual-fuel burners and for burners of stationary air heaters (WLE to DIN 4794).

The difference between series 01 and 02 lies in the duration of the safety time for the pilot burner of burners using pilot gas valves.

For

atmospheric burners of high capacity,type LFL1.638 is available.

For burner controls used with burners in continuous operation,

types LGK16... .
 型号表

LFL1.122 Series 02LFL1.133 Series 02LFL1.322 Series 02LFL1.333 Series 02LFL1.335 Series 01LFL1.622 Series 02LFL1.635 Series 01LFL1.638 Series 01
t11093631.537.56667.567.5
t223232.522.52.5
t2’-3--5-55
t343465455
t3’----2.5-2.52.5
t466101212.51012.512.5
t4’----15-1515
t543101212.51012.512.5
t61014.5121815121515
t723232.522.52.5
t8302960727896105105
t923235257.5
t10668121081010
t11optionaloptionaloptionaloptionaloptionaloptionaloptionaloptional
t12optionaloptionaloptionaloptionaloptionaloptionaloptionaloptional
t1643465455
t131014.5121815121515
t203260-2722.5---
t1预吹扫时间,风门打开t7从开始到端口7开始工作的间隔时间(风机2开始延迟时间)
t2安全时间t8启动持续时间(没有端口11和12)
t2’安全时间或1段火安全时间t9第二安全时间
t3预点火时间,短(点火变压器连接端口16)t10从启动到空气压力监测开始的间隔时间(不包括风门运行时间)
t3’预点火时间,长(点火变压器连接端口15)t11风门打开到位的运行时间
t4从t2开始到端口19打开2段火的间隔时间t12风门运行到小火位的时间
t4’从t2’开始到端口19打开2段火的间隔时间t13允许的燃烧后时间
t5从t4结束到端口20打开比例控制或阀门的间隔时间t16直到风门给出打开命令的间隔时间
t6后吹扫时间(带风机2)t20程控器锁定后的顺序自检时间