fireye 60-1386-2 价格优惠!原装美国fireye chis
价格:电议
地区:
电 话:86 0755 86216601
传 真:86 0755 86216602

Fireye价格优惠! Fireye紫外扫描仪95UVS2-1, Fireye 95UVS2-3, Fireye 95UVS21火焰检测器,Fireye紫外线扫描仪,Fireye Relay, Fireye module, Fireye紫外传感器,fireye价格,85UVF1-1QD价格,Fireye紫外传感器,Fireye火警报警仪, Fireeye 紫外,Fireeye火焰..Fireeye 燃烧控制器

 

TheFireye® E110 FLAME-MONITOR™ System is a microprocessor based burner....60-1386-2. Surface....Refer toFireyeService Note 100 separately

 

Control-Amplifier 140º F (60º C) - 40º F (-40º C)
UV1A-UV2-UV8A-UV90 Scanner 200º F (93º C) - 40º F (-40º C)
45UV5 Scanner 200º F (93º C) - 40º F (-40º C)
48PT2 Scanner 140º F (60º C) - 40º F (-40º C)
69ND1 Flame Rod (Tip 2460º F) 1500º F (816º C) - 40º F (-40º C)

 

OBSOLETE PART NUMBER COMPONENTS
D40-5030 Control 70D40 - Amplifier 72D1R1 Type 26DF4 - Model 5030
D41-5131 Control 70D41 - Amplifier 72D1R1T Type 26DF4 - Model 5131
D40-5060 Control 70D40 - Amplifier 72DUV1 Type 25DU4 - Model 5060
D41-5161 Control 70D41 - Amplifier 72DUV1T Type 25DU4 - Model 5161
D40-5050 Control 70D40 - Amplifier 72DRT1 —
D41-5151 Control 70D41 - Amplifier 72DRT1T —

 

DESCRIPTION OF FIREYE SERIES D40-41 COMPONENTS
Control Chassis and Cover Amplifier Flame Scanner
Use with
70D40 (120VAC) 50-60 Hz
or
70D41 (230VAC) 50/60 Hz
Rectification
72DRT1 2-4 sec. FFRT
72DRT1T 1 sec. FFRT
69ND1-1000K4
69ND1-1000K6
69ND1-1000K8
1/2" mount 12" (300mm) flame rod.
1/2" mount 18" (450mm) flame rod.
1/2" mount 24" (600mm) flame rod.
Infrared (IR) “Autocheck”
72D1R1 2-4 sec. FFRT
72D1R1T 1 sec. FFRT
*72D1R3 2-4 Sec. FFRT
*72D1R3T 1 Sec. FFRT
* For specific applications see note
below.
48PT2-1003
48PT2-9003
48PT2-1007
48PT2-9007
1/2 straight mount 96" (2400mm) cable.
1/2 angle mount 96" (2400mm) cable.
1/2" straight mount 48" (1200mm) cable.
1/2" angle mount 48" (1200mm) cable.
Ultraviolet (UV)
72DUV1 2-4 sec. FFRT
72DUV1T 1 sec. FFRT
UV8A
UV1A3
UV1A6
UV2
UV90-3, -6, -9
45UV3-1050
1/2" angle mount 72" (1800mm) wire (no cable).
1/2" straight mount 36" (900mm) cable.
1/2" straight mount 72" (1800mm) cable.
3/8" straight mount 36" (900mm) cable.
90º side opening, 36" (900mm), 72" (1800mm),
or 108" (2700mm) cable.
3/4" straight mount cast aluminum housing,
72" (1800mm) wire (no cable).
70D40 Only 72DUVS4 Repetitive Self-Check
2-4 sec. FFRT
72DUVS1T Repetitive Self-Check
1 sec. FFRT
45UV5-1009
or
45UV5-1008
1" NPT mount 72" (1800mm) wire (no cable),
120VAC shutter.
or
1" BSP mount 72" (1800mm) wire (no
cable),120VAC shutter.
70D40M Only Infrared (IR) AUTOCHECK
72D1R3TM 1 sec. FFRT
For special applications see Note
below.
48PT2-1003
48PT2-9003
48PT2-1007
48PT2-9007
1/2" straight mount 96" (2400mm) cable.
1/2" angle mount 96" (2400mm) cable.
1/2" straight mount 48" (1200mm) cable.
1/2" angle mount 48" (1200mm) cable.
70D41 Only 72DUVS1T or 72DUVS4 45UV5-1007 1" BSP mount 72" (1800mm) wire, no cable.
230VAC shutter
Wiring Base 60-1386-2 Standard base for surface mounting
60-1466-2 Open base for cabinet mounting
NOTE: Infrared “AUTOCHECK” amplifier modules 72D1R3, 72D1R3T, and 72D1R3T may be used for burner applications firing special
fuel such as sawdust, sander dust, low BTU gas. The 72D1R3 type amplifiers are not to be used on any liquid

 

ACCESSORIES / SPARE PARTS
Part No. Description Used with Part No. Description Used with
4-263-1 Firetron Cell 48PT2 60-801 1/2" Coupling w/Pyrex Window 48PT2
4-314-1 UV Tube 45UV5, 45UV3 60-1199-1 1" NPT Coupling w/Quartz Window 45UV5-1009
10-88 Set of 3 orifice plugs 48PT2 60-1199-2 1" BSP Coupling w/Quartz Window 45UV5-1009
35-69 1/2" NPT Heat Insulator 48PT2-UV1 60-1257 1/2" Coupling w/Quartz Window UV1A
35-127-1 1" NPT Heat Insulator 45UV-1290 1/2" Coupling w/Quartz Lens UV1A
35-127-3 1" BSP Heat Insulator 45UV5-1007/8 60-1664-3 1" NPT Swivel Mounting Flange 45UV5-1009
46-38 Quartz Lens 45UV5 60-1664-4 1" BSP Swivel Mounting Flange 45UV5-1007/8
60-302 Swivel Mounting Flange 48PT2, UV1A 61-436 Lens Cap 48PT2

 

Flame Monitor™ 

Pub No.

Product

Pub No.

Product

133-732

 Installation Instructions EP178/EP378Using 85UVF4-1QDWR

CP-47

Test Unit for Flame-Monitor C and D Series Controls, 57AV4-5001

E-1101

E110 Flame Monitor, EB700, EC600, 60-1386-2, 60-1466-2

E-1201

E120 Flame Monitor, EB701

E-2101

E210/E211 Flame Monitor, EP113E, EP113NR, EB720, EB721 (Obsolete)

E-3001

E300 Expansion Module, E350-3, E350-6, 60-1950

E-300

E300 software to change message in the Flame-Monitor (in .zip format)

E-3201

E320 Expansion Module

 

 

EAMP1

EUV1, E1R1, E1R2, E1R3, ERT1, EUVS4

E-8101

Flame monitor accessories (ED510)

E-8002

Flame monitor accessories (E110), ED512-2, ED512-4, ED512-8,
ED580-2, ED580-4, ED580-8, ED610, ED6, 129-145-3, 129-152

EC-4851

EC485 RS232/RS485 Converter

ED-5101

ED510 Display Module, ED580-1

EP-1231

Programmer modules for EP100F, EP100S, EP200F, EP200S, EP300F, EP300S

EP-1601

EP160, EP161, EP163, EP165, EP166, EP170, EP174 Programmer

EP-2601

EP260, EP261, EP265, EP270 Programmer

EP-3801

EP380, EP381, EP382, EP383, EP387, EP390 Programmer

EPD-1601

EPD160, EPD161, EPD167, EPD170 Programmer (Obsolete)

EPD-2601

EPD260, EPD261, EPD270 Programmer (Obsolete)

EPD-3801

EPD380, EPD381, EPD382, EPD390 Programmer (Obsolete)

SN-100

 

Grounding Methods for Flame Monitor

UC-4851UC485Optically isolatedUSB to RS422/RS485converter133-731English to Arabic E110 error message translation