General specifications | ||
Signal type | Analog output | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | ≤ 30 mA | |
Power loss | ≤ 600 mW | |
Power consumption | ≤ 700 mW | |
Input | ||
Connection | terminals 5-, 6+ | |
Input signal | 4 ... 20 mA limited to approx. 30 mA | |
Voltage drop | depending on switch configuration open loop voltage of the control system < 23 V: approx. 6 V at 20 mA open loop voltage of the control system < 27 V: approx. 10 V at 20 mA | |
Input resistance | > 100 kΩ, with field wiring open | |
Output | ||
Connection | terminals 1+, 2- | |
Current | 4 ... 20 mA | |
Load | 0 ... 650 Ω | |
Voltage | ≥ 13 V at 20 mA | |
Ripple | 20 mV rms | |
Transfer characteristics | ||
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA ≤ ± 0.1 % incl. non-linearity and hysteresis | |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) | |
Rise time | 10 to 90 % ≤ 100 ms | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Protection degree | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Protection degree | IP20 | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 in) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with Ex-areas | ||
EC-Type Examination Certificate | CESI 06 ATEX 021 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I | |
Statement of conformity | PF 06 CERT 0973 X | |
Group, category, type of protection, temperature class | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2005 , EN 60079-26:2007 , EN 61241-11:2006 , EN 50303:2000 | |
International approvals | ||
FM approval | ||
Control drawing | 16-533FM-12 (cFMus) | |
UL approval | ||
Control drawing | 16-533FM-12 (cULus) | |
IECEx approval | IECEx CES 06.0001 | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |