产品阐述 | ||
24 V DC | ||
General specifications | ||
Signal type | Digital Input | |
Supply | ||
Connection | terminals 23+, 24- or power feed module/Power Rail | |
Rated voltage | 20 ... 30 V DC | |
Rated current | approx. 100 mA | |
Power loss/power consumption | ≤ 1.8 W / 1.8 W | |
Input | ||
Connection | Input I: intrinsically safe: terminals 1+, 3- Input II: non-intrinsically safe: terminals 13+, 14- | |
Input I | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Pulse duration | > 50 μs | |
Input frequency | 0.001 ... 5000 Hz | |
Lead monitoring | breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA | |
Input II | startup override: 1 ... 1000 s, adjustable in steps of 1 s | |
Active/Passive | I > 4 mA (for min. 100 ms) / I < 1.5 mA | |
Open circuit voltage/short-circuit current | 18 V / 5 mA | |
Output | ||
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 | |
Output I, II | signal, relay | |
Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7; 40 V DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Collective error message | Power Rail | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Low voltage | ||
Directive 2006/95/EC | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Protection degree | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Protection degree | IP20 | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with Ex-areas | ||
EC-Type Examination Certificate | TüV 99 ATEX 1408 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb ≤ 60 °C) | |
Statement of conformity | TüV 02 ATEX 1885 X | |
Group, category, type of protection, temperature class | II 3G Ex nA nC IIC T4 | |
Output I, II | ||
Contact loading | 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2005 , EN 60079-26:2007 , EN 61241-11:2006 | |
International approvals | ||
FM approval | ||
Control drawing | 16-538FM-12 |