电话:

 

2-channel isolated barrier
230 V AC supply
Dry contact or NAMUR inputs
Relay contact output
Line fault detection (LFD)
Reversible mode of operation
Up to SIL2 acc. to IEC 61508/IEC 61511

 

General specifications
Signal typeDigital Input
Supply
Connectionterminals 14, 15
Rated voltage207 ... 253 V AC, 45 ... 65 Hz
Power loss1.2 W
Power consumptionmax. 1.3 W
Input
Connectionterminals 1+, 2+, 3-; 4+, 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Output
Connectionoutput I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I, IIsignal ; relay
Contact loading253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Mechanical life107 switching cycles
Transfer characteristics
Switching frequency≤ 10 Hz
Directive conformity
Electromagnetic compatibility 
 Directive 2004/108/ECEN 61326-1:2006
Low voltage 
 Directive 2006/95/ECEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degreeIP20
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-areas
EC-Type Examination CertificatePTB 00 ATEX 2081 , for additional certificates see www.pepperl-fuchs.com
 Group, category, type of protection II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC
Directive conformity 
 Directive 94/9/ECEN 60079-0:2009, EN 60079-11:2007 , EN 61241-11:2006
International approvals
FM approval 
 Control drawing116-0035
UL approval 
 Control drawing116-0145
CSA approval 
 Control drawing116-0047
IECEx approvalIECEx PTB 11.0031
 Approved for[Ex ia] IIC , [Ex ia] IIIC , [Ex ia] I