General specifications
Signal typeDigital Input
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 50 mA
Input
Connectionterminals 1+, 2+, 3-; 4+, 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I > 6 mA
Output
Connectionoutput I: terminals 7, 8 ; output II: terminals 8, 9
Signal level1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current
0-signal: switched off (off-state current ≤ 10 μA)
Output I, IIsignal ; electronic output, passive
Collective error messagePower Rail
Transfer characteristics
Switching frequency≤ 5 kHz
Directive conformity
Electromagnetic compatibility 
 Directive 2004/108/ECEN 61326-1:2006
Conformity
Electrical isolationIEC 62103:2003
Electromagnetic compatibilityNE 21:2004
Protection degreeIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degreeIP20
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-areas
EC-Type Examination CertificatePTB 00 ATEX 2035 , for additional certificates see www.pepperl-fuchs.com
 Group, category, type of protection II (1) G [Ex ia] IIC
II (1) D [Ex ia] IIIC
EC-Type Examination CertificateDMT 01 ATEX E 133
 Group, category, type of protection I (M1) [Ex ia] I
Statement of conformityTüV 99 ATEX 1499 X , observe statement of conformity
 Group, category, type of protection, temperature class II 3G Ex nA II T4
Directive conformity 
 Directive 94/9/ECEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
International approvals
FM approval 
 Control drawing116-0035
CSA approval 
 Control drawing116-0047
IECEx approvalIECEx PTB 05.0011
 Approved for[Ex ia] IIC , [Ex ia] I , [Ex ia] IIIC